How to Adjust Volvo Diesel Engine Speed Regulator
by Starlight Generator dieselgeneratortechUsually, engine regulator has a
factory setting that has been optimized to suit the most common generator set
applications. Use the VODIA tool (including EMS software), to read and adjust
the P, I and D sections of the engine speed regulator. Adjustment is done to
obtain more stable and even engine running, and to configure the engine for
specific generating set applications.
PID = Proportional, Integrating,
Differentiating
P-value amplifier (Gain),
amplification of the difference between the actual value and the set value.
A reduced value (Fig. 1) gives a
weaker reaction to engine speed differences. Reduce the P-value to reduce
oscillations arising from large differences in speed/load application.
An increased value (Fig. 2) gives
a shorter response time. Increase the P section for faster compensation to
large differences in engine speed/engine loading.
I-value stabilizes (Stability),
reacts to the time of the speed deviation.
A reduced value (Fig. 3)
increases the time taken by the system to respond after a load change. Reduce
the I section to reduce the oscillations which are caused by slow application
of engine loading.
An increased value (Fig 4) gives
a shorter response time. Increase the I-value to provide better load response
for slowly increasing loads.
D-value compensates (Derivative).
Reacts to fast changes of engine speed/load.
A reduced value (Fig 4.) gives a
greater sensitivity to fast changes of engine speed/load. Reduce the D-value to
reduce oscillations caused by fast changes.
An increased value (Fig. 5) gives
a reduced sensitivity to fast load changes. Increase the D-value to provide a
better ability to compensate for fast changes.
Adjustment
of PID regulator
1. Start the engine.
2. Select the “Engine with
mounting and equipment” and then “Reinforcement and Stability, calibration”
function groups in the VODIA tool.
3. When calibration is started,
certain conditions must be met, such as that the engine must be running and
must have reached a certain engine temperature.
4. Select “High” or “Low”.
High: when one is far from the
nominal engine speed, i.e. to improve load response.
Low: when one is close to the
nominal engine speed point, i.e. to increase stability.
5. Run the engine at the working
speed and working temperature.
In cases where the engine needs
to be adjusted, in-crease or reduce the values of the P and I sections until
unstable (oscillating) engine speed is obtained. Then increase/decrease the
parameters until the engine speed is stable again.
6. If the engine is still
unstable, increase/reduce the D section until engine speed only increases
slightly when load is applied (or removed), please refer to figure 6.
NOTE: The few times that the
D-value may need to be adjusted include cases where the application has a
flexible coupling or extremely low flywheel inertia.
7. Adjust the P and I sections
again as above, if necessary.
8. Check engine response as fig.
6.
9. Repeat the procedure in the
other position, “High”/“Low” if necessary.
10. To reset to factory settings,
use the reset button above the PID settings.
11. Click “Continue” to finish
calibration and follow the instructions to save the current settings in the
control unit.
Frequency
alteration, EMS2
The routine for altering the
engine speed on the TAD734GE is not the same as for, i.e. D12. There is no
system reset on the EMS2 unit, and the routine is therefore completely
different.
With Volvo
Penta CIU
If the engine is a 1500 rpm or
1800 rpm, the frequency selector must be OPEN when you start the adjustment.
OPEN selects the primary engine speed, CLOSED selects the secondary engine
speed.
Routine, with
no system voltage applied:
1. Turn on the ignition with the
starter key or switch. 2. Change the frequency selector (open or closed). 3.
Send a stop request by pressing on the stop button.
The whole procedure (steps 1 to
3) may not take longer than 10 seconds.
Routine,
with system voltage applied:
1. Send a stop request by
pressing on the stop button.
2. Change the frequency selector
(open or closed).
3. Send a stop request by
pressing on the stop but-ton.
The whole procedure (steps 1 to
3) may not take long-er than 10 seconds.
With DCU
Turn on the ignition and change
the parameter in the DCU.
With SAE
J1939 (CAN)
Customers who use their own CAN
bus-based control unit, must send certain messages to the engine (TAD734GE) in
the same way as for the Volvo Pentas CIU, in order to change from 1500 to 1800
rpm (or vice-versa).
Routine,
with no system voltage applied:
1. Turn on ECU.
2. Change the frequency selection
in the
VP_STATUS-message (open or
closed).
3. Send a stop request in a
VP_STATUS-message.
The whole procedure (steps 1 to
3) may not take longer than 10 seconds.
Routine,
with system voltage applied:
1. Send a stop request in a
VP_STATUS-message.
2. Change the frequency selection
in the
VP_STATUS-message (open or
closed).
3. Send a stop request in a
VP_STATUS-message.
The whole procedure (steps 1 to
3) may not take longer than 10 seconds.
NOTE: We are authorized as Volvo
diesel generator OEM and can provide 85KVA to 750KVA Volvo power generator. Volvo engine performance corresponds to ISO 3046, BS 5514 and DIN 6271.
Sponsor Ads
Created on Sep 19th 2018 20:25. Viewed 362 times.