Engine Connection and Parameter Setting
by Generator D. Diesel Generator
Engine Connection and Parameter Setting
Volvo Connection and Parameter Setting
TD/TAD420VE, TD/TAD520GE, TAD520VE, TAD530GE, TAD531GE, TAD532GE, TAD620VE, TD720GE, TAD720GE, TAD720VE, TAD721GE/VE, TAD722GE/VE, TAD730/731/732/733GE
Connection
Control unit
The control unit must be installed separately from the engine. Control unit working temperature must be between - 40 °C to +85 °C.
Accelerator pedal (VE engines)
Idling: 0-5 V (standard value 0.3 V)
Full throttle: 0-5 V (default value 4.6 V)
A fault code is generated when the voltage is:
U > 4.9 V (standard value)
U < 0.1 V (standard value)
Engine speed potentiometer/external voltage input (GE engines)
Rotary potentiometer for fine adjustment of Volvo engine speed (GE engines)
On 1500 rpm or 1800 rpm GE engines, the Volvo engine speed can be finely adjusted ±5 %. A fault code is generated when the voltage is:
U > 4.8 V (standard value)
U < 0.2 V (standard value)
This accelerator pedal/potentiometer corresponds to the control unit standard value (0.5 V or 4.5 V respectively).
The end position resistor is used to detect electrical faults in the accelerator/potentiometer (end position resistors are built into many accelerators/potentiometers and do not need to be added in these cases).
1500/1800 rpm switch
This function makes it possible to switch engine speed between 1500 and 1800 rpm. Switch type, two-position (NO).
Droop switch
The switch must be closed to obtain droop. Switch type, two-position (NO).
Alarm, low oil pressure
Max. power 3 W
Voltage 12 V/24 V
Alarm, high coolant temperature
Max. power 3 W
Voltage 12 V/24 V
Tachometer
Tachometer used, graduated 0-2600 rpm and with adjustable input frequency.
44 pulses/r (420/620 engines)
48 pulses/r (520/720 engines)
Diagnostic lamp
Max. power 3 W
Voltage 24 V
Diagnostic button
Switch type, closing (NO), spring biased.
To read the fault codes, please refer to the “Fault finding” chapter.
VODIA input
Deutsch 6-pin connector
To read the fault codes, please refer to the “Fault finding” chapter.
Parameter setting
Adjustable parameters