Preparation Before Starting Volvo Diesel Generator Set
by Starlight Generator dieselgeneratortechPreparation Before Starting Volvo Diesel Generator Set
① Complete inspection
a.
The switch of the control panel should be turned off before inspection, and be
careful not to short-circuit the battery output electrode.
b.
Re-clean and inspect the machine room to ensure that there are no flammable and
explosive materials around the unit, ensuring smooth and unobstructed air in
and out of the machine room.
c.
Thoroughly inspect and ensure that the electrical and control parts are
connected correctly, in good contact, reliable, and without aging.
d.
Check the reliability of the fastener and throttle adjustment system, confirm
that the operating mechanisms are flexible, lightweight, and reliable, and
check the pre-tightening of the water pump belt, charger belt and fan belt.
e.
Clean the surface of the generating set, especially the rotating part of the
unit to ensure that there are no foreign objects, check to ensure that there is
no coolant, fuel, oil leakage.
② Check the oil level
Check
to ensure that the oil level is between the highest and lowest marks and as
close as possible to the upper limit.
③ Check fuel level
a.
Note that unfiltered fuel should not be injected into the diesel engine under
any circumstances.
b.
Check the fuel quantity in the fuel tank and add suitable fuel if necessary.
c.
When the unit starts for the first time or stops for a long time and then
starts again, check to make sure there is no air in the fuel. If there is air,
loosen the air bleed screw on the diesel filter and pump the fuel to the air
bleed screw with the manual fuel pump, drain the air in the fuel system, and
tighten the bleeder screw.
④ Cooling level
Check
the coolant level to be within 5cm of the filling cover to ensure that there is
no obstruction outside the radiator.
⑤ Check the air filter
a.
Do not operate the diesel engine without air filter.
b.
Check the air filter blockage indicator. If the indicator is red, replace the
air filter.
⑥ Check battery level
Close
the power switch and check the battery voltage from the control panel. If it is
less than 22V and cannot meet the startup requirements, the battery needs to be
charged.
⑦ Governor fuel quantity control
For
the mechanical speed regulating unit, the fuel quantity control handle of the
mechanical governor should be placed at the throttle position of about
800r/min; the electronic speed regulating genset does not need to be adjusted.