Perkins Generator Frequency Is Lower Than 50Hz
1.Check the working
situation of cylinder. After running speed of diesel generator is about
700r/min, check the temperature of exhaust pipes of each cylinder by hand. If the
temperature of cylinder is different from others, it is a problem of cylinder.
If the temperature of cylinder is the same, it is not a problem of cylinder.
2.Check diesel oil
pressure. First, remove the oil outlet pipe of the oil pump, block the oil
outlet hole with one hand, and press the handle of the oil pump repeatedly with
the other hand to observe whether the oil pressure is normal.
3.Check high pressure
oil pump. Remove the side cover plate of the high-pressure oil pump, run the
diesel generator set, then carefully observe whether there is any leakage of
diesel oil between the high-pressure oil pump and the pump body. If there is
oil leakage, it shows that the clearance between the plunger and the plunger
sleeve of the oil pump channels oil, which leads to insufficient oil supply in
the low-pressure oil pipeline, power decline. So the speed can't reach the
rated speed.
4.Check whether there is
impurity or not. Check the filter screen of the oil pump after 100kw Perkins
diesel generator shout down. If there is no impurity, the operation will be
normal.
5.Check replacement.
After replacing the new oil pump, start the diesel generator and observe
whether the tachometer is displayed at 1500r/min after the speed is raised to
the standard speed. After exciter excitation, the frequency of the generator
set will be displayed at 50.5Hz, at time, if reduce the speed, the frequency
will be displayed at 50Hz. Then the diesel generator set will be able to
operate normally.
When there is problem in
diesel generator, if you do not have technology and knowledge in generator
faults, it is better not to disassemble the generator set by yourself, must
operate under professional engineers.
In order to let our
generator set run better, maintenance is also important.
Recently generator
enterprises put forward new ideas for daily maintenance: taking preventive test
as the center, replacing parts, overhauling or replacing three filters should
be based on full load test machine. In order to discover the potential safety
hazards of gensets in operation, preventive test refers to the periodic
full-load test of gensets that have been put into operation in accordance with
the specified test conditions, test items and test cycles, It can simulate the
real situation of power failure and provide objective basis.
New
methods of daily maintenance:
Inspection of four
leakages, surface, starting battery, oil and fuel of diesel Generator Set.
No load monthly, the
time of no load can not over 5 minutes.
Full-load test of diesel
generating sets and power mutation test.
Replace the three
filters according to the running time of the diesel generator.
Clean and improve the
environment of generator room
After replacement of
spare parts and the three filters, or overhaul, the full-load test machine must
be judged.
Benefits
of full-load test:
It can correct the
nominal power of the genset, keep abreast of the actual situation of the diesel
genset at any time, so that customers can have a good idea of the operation and
use electricity safely.
Obtain the performance indicators
of the genset, judge the real reason of the performance decline, provide
scientific basis for replacing the three filters, and reduce maintenance costs.
To judge whether the
expected purpose can be achieved after overhaul
Long-term full-load test
can effectively remove coke deposit, prolong diesel genset overhaul time and
save cost.
Provides the basis for
the abandonment time of Perkins diesel generator, and enables customers
to rationally arrange the use of units.