How to Deal With Low Frequency Shutdown of Generator?
by Starlight Generator dieselgeneratortech1.Check the working
situation of cylinder. After running speed of diesel generator is about
700r/min, check the temperature of exhaust pipes of each cylinder by hand. If
the temperature of cylinder is different from others, it is a problem of
cylinder. If the temperature of cylinder is the same, it is not a problem of
cylinder.
2.Check diesel oil
pressure. First, remove the oil outlet pipe of the oil pump, block the oil
outlet hole with one hand, and press the handle of the oil pump repeatedly with
the other hand to observe whether the oil pressure is normal.
3.Check high pressure
oil pump. Remove the side cover plate of the high-pressure oil pump, run the
diesel generator set, then carefully observe whether there is any leakage of
diesel oil between the high-pressure oil pump and the pump body. If there is oil
leakage, it shows that the clearance between the plunger and the plunger sleeve
of the oil pump channels oil, which leads to insufficient oil supply in the
low-pressure oil pipeline, power decline. So the speed can't reach the rated
speed.
4.Check whether there is
impurity or not. Check the filter screen of the oil pump after 100kw Perkins
diesel generator shout down. If there is no impurity, the operation will be
normal.
5.Check replacement.
After replacing the new oil pump, start the diesel generator and observe
whether the tachometer is displayed at 1500r/min after the speed is raised to
the standard speed. After exciter excitation, the frequency of the generator
set will be displayed at 50.5Hz, at time, if reduce the speed, the frequency
will be displayed at 50Hz. Then the diesel generator set will be able to
operate normally.
Sponsor Ads
Created on Oct 10th 2019 01:39. Viewed 265 times.