Guide for Starlight Generators Maintenance and Overhaul
In last two articles, we have introduced Starlight TFW Series generators detailed information and its inspection methods. In this post, you will learn the maintenance and overhaul of the alternators.
1. Maintenance.
a. Generator should be installed
in the dry, clean, ventilating place, and to prevent the direct contact of wind
driven dirt, rain, snow and sunlight.
b. Take note of the ventilation
and heating of generator at times, and the current and voltage don't exceed the
rating data.
c. The generator should not be
operated at the place that full of water vapor,dust and flammable gas.
d. In general, maintenance
intervals will depend upon operating conditions. Routine overhaul should be
made frequently.
2. Major overhaul
a. Measure insulating resistance
with 500V Meg-ohm meter. If the reading is less than 2MΩ, the generator should
be dried. (Must disconnect AVR with generator during measuring).
b. Replace the grease in bearing
housing, and clean the surface of two shield bearing or replace the bearing.
c. Clean the interior of
generator by blowing, and take care of the all junctions.
d. Inspect all living parts, and make sure joint nut tight and contact well.
3. Overhaul attention.
a. Take care of the disassemble
parts, and avoid to bump each other or missing.
d. Disassemble bearing and
bearing cap should be covered by clean paper to prevent dirt, and replace the
dirty grease.
e. After the generator
reassembled, rotate the rotor slowly, ensure there are not abnormal sound and
halt.
f. The bracket screws should be
driven crosswise, can't drive the screws one by one.
VIII. Paralleling operation.
Sx440 voltage regulator may be
supplied for paralleling operation, if necessary, customer must take note of it
in order. Consult with the factory for further information relative to parallel
operations.
IX. THYRISTOR OR SCR LOADING.
Solid state electronic control
devices which utilize thyristor or SCR firing circuit its (such as variable
frequency induction motor control precision motor speed control, no break
powered battery charges etc.) may introduce high frequency harmonics which
adversely affect, or totally distort the normal wave form of generator. This
creates additional heat in the generator winding and may cause the generator to
overheat. Problems which can occur are not limited to the generator, poor wave
shape may adversely effect the thyristor devices, the equipment they power, and
any other connected load. Please contact the factory for application
assistance.
X. Notice:
1. AVR. wiring can't be connected
wrong. The terminal '2' and '3" are connected to the tap "U3"
and 'W3" of generator winding. It is used for 200 volt, if used for 400
volt , the AVR. would be damaged.
2. The terminal "1" and
"2" of AVR. should be shorted with jumper wire. If the external
potentiometer is used for remote adjusting voltage, the potentiometer would be
connected to the "6" and "7". Or the AVR. may be damaged
without connecting.
3. Boost exciting must use the
"12V" battery , and the generator must be stopped. Using
"24W" battery or boosting the excitation in rotating, the AVR would
be damaged.
4. The generator runs at "50
Hz" or "60Hz", should ensure the wiring right, or maybe affect
AVR working.
5. Before shut down the
generating set, first turn off the output switch, then speed down the engine.
6. Take care of the contact of
the plug and sockets, ensure them close contacting each other.
7. If the generator can't built
up, first of all, look for the causes, such as: fuse; wiring; residue voltage,
etc. Please don't adjust the potentiometer and boosting excitation before known
the causes.
8. If the engine runs at idle
speed, please don't adjust the potentiometer and boost excitation.
9. Adjusting the voltage and stability potentiometer, please use small screw-driver and rotate slowly.