Generator Droop Control and Its Modes
Generator droop control is to select the
frequency droop characteristic curve (Droop Character) similar to the
traditional generator as the micro-source control method, that is, to obtain
stable frequency and voltage through P/f droop control and Q/V droop control
respectively.
Generator
Droop/Isochronous mode analysis
The ISOCH mode is the
no-difference mode, but this mode is used when the generator is running, that
is, set the frequency (Speed), and then the positive feedback value is adjusted
by the load change to achieve a stable frequency. When two or more generators are
running in parallel, if the ISOCH mode is adopted, the speed regulation ring of
each generator will act when the load changes. Because each speed regulating
ring is carried out separately, the speed regulation will be uneven and the
adjustment will be too larger or too small, causing the generator to run off.
However, if the speed regulation ring of multiple generators are connected
together in the ISOCH mode, then the adjustment parameters can be corrected to
achieve parallel operation of multiple generators and stable frequency
operation.
Droop is a differential
mode. Droop itself means drooping, that is, its speed and load curve is a
drooping straight line (ISOCH mode is a parallel straight line of X-axis), and
the speed control system will modify the frequency adjusted by the
speed-regulating ring according to the load. The adjusted frequency, which is
not the frequency we want to stabilize, but requires a secondary speed (such as
manual) in order to achieve a stable frequency. The purpose of this is to
prevent the generator from being overloaded or being reversed to cause a trip
when the load rate of the generator set is suddenly high and low.
Two operating modes of
the generator set: 1. Droop mode, the speed is sacrificed with load. 2. ISO
mode, using PMS to achieve constant speed operation mode of the generator. Both
Droop and ISO refer to the speed regulation characteristic mode of the governor,
which is differential speed regulation and non-differential speed regulation.
Active power output
regulation
1.1 Control mode
It is divided into
Droop, Isochronous and BaseLoad modes. The generator only works in Droop and
Isochronous mode when the main circuit breaker is broken. The BaseLoad mode may
be effective when the main circuit breaker closes and the generator runs with
load.
1.2 Droop mode
Droop refers to changing
the speed and frequency of the generator to proportionally change the load.
That is, when the load of the generator increases, the speed or frequency is
reduced by simple load feedback.
When the generator is
running at full load, the Droop mode can proportionally reduce the speed of the
generator. Given a suitable DRP value, the generator will always produce the
same power at a fixed frequency. Therefore, the DRP mode is sometimes called
the percent speed regulation mode.
If all generating sets
are set to the same DRP mode, they will distribute the load correspondingly to
each other. The load size depends on their speed setting. If the system load
changes, the frequency of the system will also change. At this point, the speed
given value will need to be changed to offset the change in feedback and return
the system to its original frequency. In order for all the generators in the
system to maintain the original power distribution state, each generator set
needs to make the same change at the same time.
In DRP mode, when a
generator set is connected to the system, the load control will not load the
generator at the moment when the main circuit breaker is closed, that is to
say, the generator load is set at zero. At this point, the input control point
of LoadRaise must be used to make the controller load the generator. As long as
the generator is operating in DRP mode, the user can increase/decrease the load
of the generator at any time through the load adjustment switch.
1.3 Isochronous mode
Synchronous mode means
that the generator is always running at the rated synchronous speed regardless
of its power. The ISC mode has no power feedback link, so in most cases it can
only be applied to the case where only one generator is running in the grid.
When more than two generators are running in parallel, there must be a load
feedback method to manage the load of each generator.
1.4 Load distribution in
ISC mode
The EGCP-3LD can
distribute the load between generators operating in multiple ISC modes. The
feedback signal is provided by the LON network and the speed can be kept
constant as the load changes.
The LON information is
based on the rated power of the generator. If the rated capacity of each
generator is different, LON will maintain their same load percentage.
The EGCP-3LS
automatically adjusts the load distribution between generators operating in
multiple ISC modes to maintain the output frequency at the rated value.
1.5 BaseLoad mode
The BSL mode is similar
to the DRP mode and is used when running in parallel with an infinite grid or
facility. The advantage is that the frequency does not change when it is
separated from the facility. Simply set the trimming signal to zero to separate
from the facility and return to ISC mode operation.
In BSL mode, the load reference
can be changed either internally or remotely. Remote refers to the method of
inputting through an external analog signal.
Post Your Ad Here
Comments