Cummins Generator Fuel, Oil and Coolant Requirements
by Starlight Generator dieselgeneratortechFuel requirements for
Cummins generator set: Use high quality light diesel oil with lower
temperature. Because of the higher temperature fuel used, the filter can be
clogged to reduce power and cause engine starting difficulties.
After Cummins generator
is shut down, remove the water from the fuel filter in a hot state and replace
the filter regularly (250h). If the fuel used is dirty, the filter will be
blocked in advance, and the engine power will decrease after the filter is
blocked.
Requirements
for lubricating oil of Cummins generator set:
1) Viscosity in
accordance with SAE 15W40
2) Quality meets API CD
or higher
3) Change the oil and
filter regularly (250h)
Note: Engine oil of CF4
or above must be used on the plateau. Because the combustion condition of the
engine in the plateau deteriorates, the oil pollution is very fast, the oil
life below CF4 level is less than 250h, and the oil change period should be
shortened by half. Oil that exceeds the life of the engine will result in the
engine not being properly lubricated, the wear will be intensified, and early
failures will occur.
Coolant
requirements for Cummins generator set:
1) Use water filter or
add DCA dry powder as required to prevent corrosion, cavitation and scaling of
the cooling system.
2) Check the seal of the
pressure cap of the water tank and the leakage of the cooling system to ensure
that the boiling point of the coolant does not decrease and the cooling system
is normal.
Note: The
generator set operating in cold areas should use ethylene glycol + water
coolant or antifreeze approved by manufacturer to meet the environmental
conditions. It is also necessary to check the DCA concentration and freezing
point in coolant regularly.