Why a Power Generator Is Running But no Voltage Is Produced?
by Starlight Generator dieselgeneratortechIf the generator has not
been run for a long time or if it was left with a load connected while it was
not running, then one of the more likely causes is loss of residual magnetism.
Most small generators do not have magnets but have two sets of coils, one that
spins and one that is stationary. When these generators start up, if there is
no magnetic field at all, then there will be no power created. Usually there is
a very small residual field from the last time the generator ran which make a
very small amount of power which then makes the magnetic field stronger which
makes more power and this cycle continues until the generator is producing its
rated power (after a very short period of time, usually by the time the engine
has spun up to normal operating speed).
There are a few methods
of restoring a generator residual magnetism
12
Volt Generator Battery Method
Locate the voltage
regulator for your generator.
Unplug the two wires
that connect to the generator brushes. Normally one is red and the other is black
or white.
Connect the black or
white to the generator ground battery terminal.
Plug in a light, turn on
the generator breaker or switch and start the motor.
Connect the battery +12
volts (red cable) to the red wire on the terminals you removed for three
seconds.
Remove your wires and
replace the plug. The generator should now be producing power again.
Make sure you unplug the
brush wires from the automatic voltage regulator or you will damage the
regulator. Do not contact the voltage regulator or other wires as dangerous
voltages may be present that can cause electric shock.
Electric
Drill Method
Plug in an electric
drill into the generator receptacle.
If the drill is
reversible, move the direction switch to the forward position.
While depressing the
trigger on the drill, spin the drill chuck in reverse direction. This will
excite the field and the generators will now produce electricity. If spinning
the chuck one direction does not work, try spinning the chuck in the other
direction as you may have the reverse switch positioned backward.